A Measurement Method for Magnetic Loss of Transmission Line Fittings Based on Thermal-Equilibrium Correction
-
Abstract
Ferromagnetic components of overhead line fittings (suspension clamps, tension clamps, etc.) generate hysteresis and eddy-current losses under alternating current, which represent a long-underestimated source of power loss in transmission lines. Such magnetic loss is far smaller than bulk I2R loss of conductors, and its measurement is coupled with current fluctuations, conductor temperature rise, and varying heat-dissipation conditions; consequently, conventional power-difference methods (with versus without fittings) cannot effectively isolate true magnetic loss. To address these difficulties, a refined measurement method for magnetic loss of line fittings based on thermal-equilibrium correction was proposed in this paper. A current-stabilized platform was employed to ensure current consistency between two measurements; current-carrying layer temperature was determined through four-layer temperature measurements on steel core, aluminum strands, armour rods, and conductor surface; and measured power was corrected to a common reference temperature according to resistance temperature coefficients, whereby small magnetic loss was separated from large conductor loss. The apparent “negative-loss” phenomenon observed for preformed suspension clamps was mechanistically explained by combining thermo-electric coupled finite-element simulation with tests conducted in accordance with IEC 61284:1997: it arises from parallel current paths of armour rods, which reduce DC resistance, enlarge equivalent diameter, and enhance auxiliary heat dissipation, so that energy-saving gains outweigh the fitting’s own small magnetic loss. Results indicated that suspension clamps with aluminum-alloy armour rods did not increase total line loss but rather reduced overall power consumption. The proposed method could be used as a reference for magnetic-loss evaluation and selection of energy-saving fittings.
-
-